JR-SS Electronic Overload Relay
1.Application
JR-SS electronic overload relay is suitable for AC 50/60Hz, voltage up to 600VAC and currentup to 60A. It is used as overload and phase loss protection, independently adjustable startingand trip delay, visual current setting aid and trip indication, fail safe protection (N type) andelectronic shear pin function. The product conforms to IEC60947-1 standard.
2.Specification
JR-SS electronic overload relay is suitable for AC 50/60Hz, voltage up to 600VAC and currentup to 60A. It is used as overload and phase loss protection, independently adjustable startingand trip delay, visual current setting aid and trip indication, fail safe protection (N type) andelectronic shear pin function. The product conforms to IEC60947-1 standard.
2.Specification
Type | JR-SS | ||
Current range | 05)0.5-5A(scale 6.5A) | ||
30)3-30A(scale 35A) | |||
60)5-60A(scale 70A) | |||
Rated voltage | 600VAC,50/60Hz | ||
Operation setting | D-TIME | 0.2-30seconds | |
O-TIME | 0.2-10seconds | ||
Accuracy | Current | ±10% | |
Time | ±15% of max.time set value | ||
Time characteristics | Definite time | ||
Control voltage | 220)Voltage free(90~260)VAC,50/60Hz 440)Voltage free(320~480)VAC,50/60Hz Other voltage optional. | ||
Current sensing | 2 CTs | ||
Output contacts | Contacts | SPDT 3A/250VAC Resistive | |
Condition | N Type | Normally energized:95-| |-98closed | |
R Type | Normally De-energized:95-|/|-98closed | ||
Reset | Manual or remote electrical by interrupting supply | ||
Environment | Temp. Run | Run | -20+70 deg.oC |
Store | -30+80 deg.oC | ||
Humidity | 45~85% RH,non-condsing | ||
Insulation | Between casing and circuits:Over 10MΩ with DC 500V megger | ||
Dielectric strength | 1)Between casing & circuits:AC 2000V,60Hz,1 min | ||
2)Between contacts:AC 1000V,60Hz,1 min | |||
3)Between contacts:AC 2000V,60Hz,1 min | |||
Power consumption | Under 2W | ||
Mounting | 35mm Din Rail(D) | ||
The run-up current of motor(starting current)does relay trip because overcurrent protection of AJR-SS is not applied during motor run-up time. |