Designed for central air conditioning and heating equipment |
Features
1.Any position mounting 2.Interchangeable mounting plate 3.Low wattage coil 4. Double break contacts ensure positive make and break. |
Specifications |
Insulating material |
Contact block and carrier are high quality electrical-grade thermosetting resin |
Temperature range |
-40F to 150F |
Mechanical life (no load) |
Conforms to UL and ARI specifications |
Electricl life |
Conforms to UL and ARI specifications |
Weight (approximate) |
16 oz |
Coils Frequency |
50/60Hz |
Coil insulation |
Class B(130oC ) 24 through 208/240 Volts AC |
Termination |
Pressure connector and double 1/4 Q.C |
Operate |
85% of nominal coil voltage; 110% maximum safe operate |
Duty cycle |
Continuous | |
Coil data -25 and 30Amp,600volt three pole normally open (3.P.N.O) |
Steveco Number 25 Amp 30Amp |
Voltage AC |
Ress DC OHMS |
Current MA |
Nominal VA |
Max. inrush |
AMC2-160 AMC2-163 |
24 |
9.2 |
187 |
4.5 |
52 |
AMC2-161 AMC2-164 |
120 |
180 |
37 |
4.5 |
52 |
AMC2-162 AMC2-165 |
208/240 |
720 |
19 |
4.5 |
52 | |
Contact ratings --25 and 30Amp,600volt three pole normally open (3.P.N.O) |
Type |
Voltage |
277VAC |
480VAC |
600VAC |
AMC2-160 thru AMC2-162 |
Full load Lock rotor Resistive |
25 A. |
25 A. |
25 A. |
150 A. |
125 A. |
100 A. |
40 A. |
40 A. |
40 A. |
AMC2-163 thru AMC2-165 |
Full load Lock rotor Resistive |
30 A. |
30 A. |
30 A. |
180 A. |
150 A. |
120 A. |
50 A. |
50 A. |
50 A. | |
Coil data -40 Amp ,600 volt three pole normally open (3.P.N.O) |
Steveco Number 40 Amp |
Coil Voltage AC (60Hz) |
Ress DC OHMS |
Current MA |
Nominal VA |
Max. inrush VA |
AMC2-170 |
24 |
7.2 |
187 |
4.5 |
52 |
AMC2-171 |
120 |
180 |
37 |
4.5 |
52 |
AMC2-172 |
208/240 |
720 |
19 |
4.5 |
52 | |
Contact ratings -40 Amp ,600 volt three pole normally open (3.P.N.O) |
Type |
Voltage |
277VAC |
480VAC |
600VAC |
AMC2-170 thru AMC2-172 |
Full load Lock rotor Resistive |
40 A. |
40 A. |
40 A. |
240 A. |
200 A. |
160 A. |
50 A. |
50 A. |
50 A. | |
|